Coen, you are confusing using the right solution, verses trying to bend everything around using 1 thing. Trying to find ways to make everything work on one gauge wire is down right silly and impractical.
No, it's actually not silly and also very practical. Below 1,5mm^2 you reach the area where you don't want to get smaller because stuff breaks too easily from mechanical stresses. Go just 1mm^2 up and you're already fine for just about everything in a household. That leaves the cooktop. Use 3-phase and voila; everything works just fine with 2,5mm^2. Minimal amound of different wires in the van.
What you do is bend everything to fit in 110V. And as it turns out... it's rather impractical.
Also; how is using one gauge now impractical but Festool using two different gauges impractical at the same time? (Thx
@Alex )
Same for the sockets. We could do as you do there. We could get rid of our high current receptacles and hardwire things in, but that would be a step backwards.
Use 230/400 and voila; all those problems are gone because a 15A socket will be fine for about everything.
We could run multiple parallel wires to get the same power to a location without changing wire size, but that's wasteful verses just using the correct size wire. We do have some instances were this is done. Some items with multiple heating elements do this, such as tankless water heaters, they might have 2-3 parallel circuits.
The waste is not in the European system. Let's figure it out; a 11 kW heater here is connected with 3-phase 16A, requiring a grand total of 4 wires (to include earth). But let's be fair; almost always the neutral is used too, so five wires of 2,5mm^2. Rolls of 100m of those fit in a Systainer IV with room to spare...
You connect the 11 kW heater in a 50A circuit requiring what? 3x16mm^2? So per meter length you use almost 4x the copper. Your voltage losses will be 2,2 as small, but current being 3 times as high you still lose 50% more in the wiring. Soooo... it won't fit in the same 19mm conduit (3/4" if you like..), it uses 4x the copper and has 50% more losses. Tell me again what is more wastefull?
Often this is because they are imported products from Europe, so it's just the 3phase design repurposed. Electric heating in HVAC might do similar as well. Sure, we could probably get to 1 wire size, but we don't want to run 6awg for everything.
I am not saying you have to use 1 wire size. My point is that your mess with different wire sizes is a consequence of using the wrong voltage. If you switch over to 230V and 3-phase, the wire size issue will just melt away.
We don't do as you keep describing since again, it's unsafe, and there is no reason to. Just run the correct size wire. Stop limiting yourself by trying to make everything work back to one thing.
What we do is perfectly safe. In addition to that the van can be one meter shorter / lower, leading to less "traffic accidents".
Our wiring isn't hard at all. You are imagining problems that don't exist.
Well, two different gauges being a problem was the whole reason for this topic. So is it a problem or not?
We don't have voltage drop issues. We run 240V power to houses, you run 230V power to houses. In the run lengths within a home that are 110V, the voltage drop will not be noticed, also we run properly sized wire. Your wires are too small.
You do know that for same power transported with half the voltage you need four times the wire cross section to get the same relative voltage drop.... right? So that works out to 10mm^2 for you where we use 2,5mm^2. Seems you are using too small wires!
Maybe you have different breakers than us. We use Magnetic-Thermal breakers. You either pull too many amps for too long to trigger it thermal, or you have a short/inrush that trips the magnetic.
Same here.
We have Arc fault breakers that detect arcs and trip them too. We don't test for impedance because it doesn't change if the breaker will trip or not.
Lol your logic is flawed. If your circuit is a long run and you live far from the transformer, your circuit impedance will rise. Especially if you use a breaker that allows for higher inrush currents (magnetric trip lower limit raised)... it can be hard to actually be able to achieve the magnetric trip with a short circuit. I'll give you an example;
In the 1970's home of my brother the circuitimpedance on his side in a kitchen outlet is 0,35 Ohms. Max fault current is 650A. Now run it to some shed... and voila; your max fault current might be <500A meaning the use of C50 breaker is not allowed.
Any such reliance is flawed. You have just made the system to complicated and sensitive, the impedance isn't going to be static anyway.
No, if it's cold it will be higher by a few %. Other than that you still don't seem to understand circuitimpedance
Some things in Europe are done well and could be said better than N.A. . Electrical isn't one of them. You will never get the engineers, safety official, etc that create NEC code to head in the direction of Europe.
Less complicated world needs safety officials. Just tell me again how multifunction testers were not a thing in the US yet are in Europe?
And from what I can find... the USA loses a multiple of lives each year (yes, also relative to population) to electrocution compared to NL.
The elements of what you have over there, exist here, they just aren't commonly used for various reasons. But we aren't going to go lowering temperature ratings on wires, reducing the size of wires, running them at the limits of their capacities. 3 Phase distribution to homes is neat, and we have such systems, they just aren't widespread as there isn't as big of a benefit as some folks think.
You are the only one who keeps bringing up temperature ratings of wire. Did you yet realize that a 110V circuit requires FOUR times more copper to have the same power losses? Power lost = heat produced. Perhaps now then you understand heat is not really an issue here.
We use the right solutions for the problem. Safety rules all in US electrical.
Aaaah! So that is why you cut off the notches of thinner gauge cords?
Saving a few bucks using smaller wires, yet increasing the fire risk is not something that will happen. Running higher voltages, thus needing even more precautions when it comes to insulation/isolation, verses just pulling some more amps thru a bigger wire is not a change that will happen.
Thru this thread, going back to the 2 cord sizes, it goes back to there being no reason for the smaller gauge cord, was festool just trying to get to a smaller wire size because they thought that was better? Or thoughts on the Kapex saga with saws burning up.
There is as much a need for the smaller gauge cord as there is for the D27 hose even though the D36 hose exists.